AVR AS440

Detailed Parameters

Sensing input

voltage

Jumper selectable.100-130 Vac 1 phase or 190-264 Vac 1 phase

frequency

50-60 Hz nominal

Power input

Voltage

100-264 V ac 1 phase

frequency

100-120 Hz nominal

output

voltage

82 V d.c. @ 200 V a.c.

Current

Continuous 4 A dc. transient 7.5A for 10 secs.

resistance

15 ohms min

regulation

+/- 1.0% (see note 1)

Thermal drift

0.03% per deg. C change in AVR ambient

Typical system response

AVR response

20 ms

Filed current to 90%

80 ms

Machine volts to 97%

300ms

External voltage adjustment

+/- 10% with 1 k ohm 1 watt trimmer

Under frequency protection

Set point

95% Hz(see note 4)

Unit power dissipation

12 watts maximum

ANALOGUE INPUT

 

Maximum input

+/- 5V dc

Sensitivity

1v for 5% Generator Volts (adjustable)

Input resistance

1k ohm

QUADRATURE DROOP INPUT

Max. sensitivity

0.07 A for 5% droop 0PF

Max. input

0.33 A

OVER EXCITATION PROTECTION

Set point

65 V dc

Time delay

10-15 seconds (fixed)

Build up voltage

4 volts @ AVR terminals

pro-list-nr
Imported accessories
Our products have always used high-quality imported accessories to ensure product stability and reliability. We know that only the best materials and accessories can produce the best products.After installation, our products have stable performance and can basically be used for 5-10 years.
Main accessories include

> Capacitor

> Resistance

> Chip

GET A QUOTE

+86 13587676206

+86 13587676206

shirlin@avrt.net

GET IN TOUCH NOW
×

GET A QUOTE

+86 13587676206

+86 13587676206

shirlin@avrt.net

GET IN TOUCH NOW
×