Variable voltage supply
40 ÷ 270 Vac
Frequency range
12 Hz ÷ 72 Hz
Precision of voltage regulation
± 1%
Precision of voltage regulation (stabilized condition)
± 0,5%
Maximum continuous output current
5 Adc
Environmental temperature
-25°C ÷ +70°C
Voltage regulation
75÷300 Vac
Transient voltage drop and overvoltage
within ± 15%
Voltage recovery time
within ± 3% of the value set, in less than 300 msec
Sensing
Single phase or Three phase
Parameters (can be programmed via software)
VOLT, STAB, AMP and Hz can be set with trimmers (default)
50/60Hz through a “jumper” (default)